This part of GB/T 12513 specifies requirements for test methods of Glazed elements for resistance performance.
GB/T 12513 Fire-resisitance tests–temperature curve shown
the fire exposure of door assemblies shall be controlled to conform to the applicable portion of the standard time-temperature curve shown. the points on the curve that determine its character are:
538°C at 5 min
795°C at 20 min
843°C at 30 min
927°C at 1 h
1010°C at 2 h
1093°C at 4 h
and the other time
GB/T 12513 Fire-resisitance tests (Chinese Standard)– Scope
- horizontal glazed element
- inclined glazed element
- vertical glazed element
- insulated glazed element
- uninsulated glazed element
GB/T 12513 Fire-resisitance tests (Chinese Standard)– value
1. Duration of fire resistance
2. Loadbearing capacity and impermeability
3. Insulation
4. Integrity
GB/T 12513 Fire-resisitance tests (Chinese Standard)– other standard
BS 476-20:Fire Tests on Building Materials and Structures Part 20: Method for Determination of the Fire Resistance of Elements of Construction (General Principles)
ASTM E 119 Standard test method for Fire tests of building construction and materials
GB/T 9978-1 Fire-resistance tests-Elements of buidling construction-part1:General requirements
GB/T 9978-3 Fire-resistance tests-Elements of buidling construction-part3:Commentary on test method and test data application.
GB/T 9978-5 Fire-resistance test-Elements of building construction- Part 5:Specific requirements for loadbearing horizontal separating elements.
GB/T 9978-6 Fire-resistance test-Elements of building construction- Part 5: Specific requirements for beams.
GB/T 9978-8 Fire-resistance test-Elements of building construction- Part 8:Specific requirements for non-Loadbearing vertical separating elements
GB/T 9978-9 Fire-resistance test-Elements of building construction- Part 9: Specific requirements for non-Loadbearing ceiling elements
EN 13501-2:Fire classification of construction products and building elements-Part 2: Classification using data from fire resistance tests, excluding ventilation services
----------------------------------------------------------------------------------------------------------------------