BS 8434-2 Assessment of the fire integrity of electric cables

Article
 
BS 8434-2 Fire integrity of electric cables–Standard

BS 8434-2 Methods of test for assessment of the fire integrity of electric cables-Part 2: Test for unprotected small cables for use in emergency circuits- BS EN 50200 with a 930 °C flame and with water spray

BS 8434-2 Fire integrity of electric cables–Scope

This British Standard specifies a method of test to be used for small unprotected cables where the requirements of BS EN 50200 are modified to use a flame temperature of (930+40)'C and the application of water spray. Compliance with the requirements of BS 5839-1:2002, 26.2e) may be demonstrated using this method.

BS 8434-2 Fire integrity of electric cables–Relative Standard 

BS 8434-1, Methods of test for assessment of the fire integrity of electric cables - Part 1: Test for unprotected small cables for use in emergency circuits -BS EN 50200 with addition of water spray.

BS EN 50200, Method of test for resistance to fire of unprotected small cables for use in emergency circuits 
 
----------------------------------------------------------------------------------------------------------------------
[ Add to Favorites ]  [ Print this page ]  [ Close the window ]  [ Back to top ]