DIN EN 60332-1-2 / EN 60332-1-2 Fire test on a single cable
DIN EN 60332-1-2 / EN 60332-1-2 Fire test on a single cable
DIN EN 60332-1-2 Fire test on a single cable - Standard
DIN EN60332-1-2: Test for vertical flame propagation for a single insulated wire or cable
DIN EN 60332-1-2 Fire test on a single cable - Test condition
Before testing, all test pieces was conditioned at (23±5) ℃ for not less than 16h at a relative humidity of (50±20) %.
DIN EN 60332-1-2 Fire test on a single cable- Requirement
When insulated wires and cables, the test is passed, if the distance between the lower end of the upper mounting and the start of charring more is over 50 mm. The flame expands by more than 540 mm from the bottom of the upper attachment to below, this must be called an error. Shall one failure recorded, two further tests perform. If both tests are passed, then the examination of individual wire or cable as passed. (Refer to DIN 5510-2 or EN 45545-2 test standard)
DIN EN 60332-1-2 Fire test on a single cable - Reference Standard
- EN45545-2: Fire protection of railway vehicles - Part 2: Requirement for fire behaviors of materials and components
- DIN5510-2: Preventive fire protection in railway vehicles; Part 2: Fire behavior and fire side effects of materials and parts, classification, requirement and test methods
- EN 60332-3-24Tests on electric and optical fibre cables under fire conditions -Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables-Category C
- DIN EN 50266-2-4:: Common test methods for cable under fire condition-Test for vertical flame spread of vertically-mounted bunched wires or cables-Part 2-5: Procedures-Category C
- EN 50266-2-5: Common test methods for cable under fire condition—Test for vertical flame spread of vertically-mounted bunched wires or cables-Part 2-5: Procedures –Category D
- EN 61034-1, Measurement of smoke density of cables burning under defined conditions -Part 1: Test apparatus
- EN 61034-2, Measurement of smoke density of cables burning under defined conditions - Part 2: Test procedure and requirements
- EN 50305Railway rolling stock cables having special fire performance -Test methods
----------------------------------------------------------------------------------------------------------------------