NF C32-070 Fire tests on cables

Article

 
 
NF C32-070 Fire tests on cables
 
NF C32-070 Classification tests on cables - Standard
 
NFC32-070: Insulated conductors and cables for installation-Classification tests on conductors and cables with regard to fire behaviour.
 
NFF16-101 – Railway Rolling Stock Fire Behavior Choice of Material
 
NF C32-070 Classification tests on cables - Brief
 
Halogen Free Control Cable With Numbered Conductors, NF C32-070 C1 is a halogen free multi-conductor, flexible power and control cable designed for use in all electrical equipment in dry, damp and wet conditions. Recommended applications include machinery, data processing equipment, ventilation and air conditioning systems. In case of fire, no corrosive gases are produced. This cable is particularly suitable for use where human life and valuable property are exposed to an extremely high risk of fire.
 
NF C32-070 Classification tests on cables - Requirement
 
A vertically installed cable or a bundle of cable is exposed to the effects of a radiating over (approx.830) and forced ventilation. Pilot flames arranged above the over burn off the emitted gasses. The test duration is 30 minutes. The cable length is 1600mm.The classification according to destroy area.
 
Then, they are submitted to the category C1 test of the NF C 32-070. Depending on the results (degraded length), they are classified in four classed A, B, C, D,
 
Class
Requirement
A
B
C
D
No ignition and no degradation beyond the upper part of the furnace
Length of degradation beyond the upper part of the furnace does not exceed 50mm
Length of degradation beyond the upper part of the furnace does not exceed 300mm
Length of degradation does not exceed the top of the furnace
 
NF C32-070 Classification tests on cables – Reference standard
 
- NFF16-101 – Railway Rolling Stock Fire Behavior Choice of Material
- DIN5510-2 : Preventive fire protection in railway vehicles; Part 2: Fire behaviour and fire side effects of materials and parts, classification, requirement and test methods
- EN45545-2: Fire protection of railway vehicles - Part 2: Requirement for fire behaviours of materials and components - R15 / R16
 
- EN60332-3-24: 2010-08 Test on Electric and Optical Fibre Cables under Fire Conditions Part 3-24: Test For vertical flame spread of vertically---Mounted bunched wires or cables Category C (IEC 60332-3-24:2000 + A1:2008)
- DIN EN 50266-2-5 Common Test Methods for Cables under Fire Conditions - Test for Vertical Flame Spread of Vertically-Mounted Bunched Wires or Cables Part 2-5: procedures – Category D
- DIN EN 50305: Railway applications. Railway rolling stock cables having special fire performance. Test methods
- DIN EN 60332-1-2: Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame
 
 
----------------------------------------------------------------------------------------------------------------------